Building in a bushfire prone area: BAL and the NCC
Editions covered: NCC 2022 (current in most states), NCC 2025 (WA, VIC, ACT) · Last reviewed 15 November 2026
If a house is in a designated bushfire prone area, its Bushfire Attack Level (BAL) shapes much of the design. It affects the windows and screens, the cladding, the decking, the gutters, the subfloor and even the evaporative cooler. The NCC itself is short on this topic. It points to AS 3959 or the NASH steel-framed standard. The rest depends on how each state maps bushfire prone land and sets the BAL. This guide explains the framework, what each BAL means, and where the states part ways.
Which edition?
- NCC 2022 applies in NSW, QLD, SA, TAS and the NT.
- NCC 2025 applies in WA, VIC and the ACT from 1 May 2026. WA and the ACT allow a 12-month transition.
- The clause numbers below (H7P5, H7D4) are the same in both editions.
Where the rules are
- NCC Volume Two H7P5: the Performance Requirement for Class 1 houses, and associated Class 10a buildings and decks, in a designated bushfire prone area. The building must:
- reduce the risk of ignition from a design bushfire
- prevent internal ignition
- stay structurally sound for the duration of the fire.
- H7D4: the deemed-to-satisfy route, which only applies in a designated bushfire prone area. The house is built to either:
- AS 3959 (construction of buildings in bushfire-prone areas; the 2018 edition is referenced), or
- the NASH Standard: Steel Framed Construction in Bushfire Areas.
- AS 3959 is cited by number only. We don't reproduce its construction tables.
Key requirements
-
Is the site bushfire prone? The state designates bushfire prone areas, not the NCC.
- In WA, the Fire and Emergency Services Commissioner designates them on the Map of Bush Fire Prone Areas.
- In Victoria, they're mapped under the building system and shown on VicPlan.
- In NSW, bush fire prone land is shown on a map certified by the Commissioner of the NSW RFS. Development there must meet Planning for Bush Fire Protection 2019 (NSW RFS).
- In SA, the Planning and Design Code identifies bushfire risk areas (SA H7D4(3)).
- Elsewhere, check with your state or local council.
If the building sits entirely outside the mapped area, H7D4 doesn't apply.
-
Get a BAL assessment: the BAL is a site-specific assessment under AS 3959. It is based on:
- the vegetation type
- the distance from the building to that vegetation
- the slope of the land.
AS 3959 has a simplified method (Method 1) and a detailed method (Method 2). WA and Victorian guidance point to accredited assessors, such as those listed by Fire Protection Association Australia.
-
The six BALs (summarised from WA Building and Energy):
- BAL-LOW: not enough risk to need specific construction requirements.
- BAL-12.5: mainly ember attack, with low radiant heat.
- BAL-19: moderate risk, with more embers and burning debris, and radiant heat up to 19 kW/m².
- BAL-29: high risk, with radiant heat up to 29 kW/m².
- BAL-40: very high risk, with increasing likelihood of flame contact.
- BAL-FZ (Flame Zone): extreme risk, with direct exposure to flames from the fire front.
-
What the BAL changes: AS 3959 sets construction requirements by BAL for:
- subfloor supports and floors
- external walls
- windows, doors, screens and shutters
- roofs, eaves, fascias, gutters and downpipes
- verandahs, decks, steps and landings
- vents, weep holes and gaps
- roof-mounted evaporative coolers
- water and gas supply pipes.
Higher BALs need tougher materials and fewer gaps. Ask the app for the AS 3959 clause for your BAL and element.
-
Associated structures: attached garages, carports, verandahs and decks may need to meet the same BAL, or be separated by construction or distance (WA Building and Energy).
- Victoria's planning guidance notes that a shed not attached to the house and more than 6 m away doesn't need to meet the bushfire standard. It cites AS 3959 clause 3.2.3.
-
Other NCC links:
- The condensation roof-space ventilation rules (Housing Provisions 10.8.3 in NCC 2022; 10.8.3 and 10.8.4 in NCC 2025) don't apply to roofs that must meet BAL-FZ under AS 3959.
- Safety glass rules (Part 8.4) still apply alongside AS 3959's glazing rules.
- In WA, check the separate fire-separation rules for roofed outdoor areas (WA Part 9.6).
How the states differ
- NSW: NSW H7D4 applies AS 3959 or NASH as amended by Planning for Bush Fire Protection (NSW RFS). BAL-FZ is excluded from the standard route and is dealt with through specific conditions of development consent. Construction can also be modified by development consent after RFS consultation, or by a bushfire safety authority under s 100B of the Rural Fires Act 1997.
- Queensland: QLD H7D4(3) switches the requirements off where the classified vegetation is:
- Group F rainforest (not including wet sclerophyll forest)
- mangroves
- grassland under 300 mm high.
- South Australia: SA H7D4(3) sets the BAL from the Planning and Design Code:
- general bushfire risk areas: BAL-LOW
- medium bushfire risk areas: BAL-12.5
- high bushfire risk areas: assessed under AS 3959
- urban interface within 500 m of a high-risk area: BAL-LOW
- urban interface within 100 m of a high-risk area: assessed under AS 3959.
- Victoria:
- In a designated bushfire prone area, the building permit applies the BAL construction requirements (Department of Transport and Planning).
- Under reg 156 of the Building Regulations 2018 (Vic), the building surveyor must accept a BAL specified in the planning scheme, or one set by a site assessment considered for the planning permit.
- Reg 157 used to make a BAL-LOW site build to BAL-12.5. It was revoked in 2026 (S.R. No. 38/2026), so the assessed BAL now applies. Confirm the BAL for your site with your building surveyor.
- The Bushfire Management Overlay (BMO) is a planning control for very high and extreme hazard areas. It requires a planning permit with defendable space, water supply and access. Land in a BMO is also bushfire prone.
- Bushfire matters already decided in the planning permit don't need to be considered again at the building permit stage (Department of Transport and Planning).
- Western Australia:
- A four-month transition applies after an area is newly designated.
- The requirements don't apply to some work on "relevant buildings", which are existing buildings that didn't have to meet bushfire standards. The concession covers work valued under $20,000, or work that doesn't increase ignition risk.
- Roof-mounted evaporative coolers installed in bushfire prone areas are building work and generally need to comply with AS 3959 (Building and Energy).
- Tasmania: TAS H7P5 replaces the national Performance Requirement. It adds vehicle access and a firefighting water supply. Its note points to the Director's Determination on bushfire hazard areas, published by CBOS. For bushfire prone area mapping and the current determination, check with your state or local council.
- ACT and NT: no H7D4 variation in the NCC schedules. For bushfire prone area mapping, check with your state or local council.
Ask the app
Upload a photo of the BAL certificate, window screens, deck boards or gutter guards, or ask:
- "What does BAL-29 mean for windows?"
- "Do I need ember screens on sliding doors at BAL-19?"
- "Does a detached shed need to meet the BAL?"
- "Does the BAL apply to an evaporative cooler in WA?"
- "In SA, what BAL applies in a medium bushfire risk area?"
Ask a bushfire question · Builder · Glazing · Carpentry · Roofing
Related checklists
- Bushfire (BAL) construction: new house (plan required)
- Bushfire (BAL) construction: renovation / extension (plan required)
- Windows, doors & glazing: new house (plan required)
- Related guides: Glazing and window safety · Condensation and wall wraps
FAQ
What does BAL stand for? Bushfire Attack Level. It measures a building's potential exposure to embers, radiant heat and flame, and sets the level of construction needed under AS 3959. There are six levels, from BAL-LOW to BAL-FZ.
Who decides my BAL? A BAL assessment under AS 3959, usually by a qualified or accredited assessor, which your building surveyor or certifier relies on. In SA, the Planning and Design Code sets the BAL for general and medium-risk areas (SA H7D4(3)). In NSW, Planning for Bush Fire Protection and the development consent also apply.
Does the BAL apply if only part of my block is bushfire prone? It depends on where the building sits. WA and Victorian guidance both say a building entirely outside the mapped area doesn't need to comply. In Victoria, if part of the footprint is inside, the whole building does.
Can I use a steel-framed house instead of AS 3959? H7D4 allows the NASH Standard for steel-framed construction in bushfire areas as an alternative. In NSW, it's subject to Planning for Bush Fire Protection and excludes BAL-FZ.
Does an existing house need upgrading if the area is newly mapped? Generally no. Building rules aren't retrospective. New work, extensions or rebuilds may need to comply, subject to state concessions such as WA's "relevant building" exemptions.
This is general guidance, not a compliance check. Always check your approved plans, your BAL assessment and any planning conditions, and the edition that applies to your permit, and confirm details with your certifier or building surveyor.
Based on content from the National Construction Code 2022 and 2025 (NCC Volume Two and the ABCB Housing Provisions), provided by the Australian Building Codes Board under the CC BY 4.0 licence. The ABCB does not endorse this guide. The standards the NCC references are cited and explained in our own words, not reproduced.
Sources
- NCC 2022 Volume Two: H7P5, H7D4, NSW H7D4, QLD H7D4(3), SA H7D4(3), TAS H7P5
- NCC 2025 Volume Two, Part H7: https://ncc.abcb.gov.au/editions/ncc-2025/adopted/volume-two/h-class-1-and-10-buildings/part-h7-ancillary-provisions-and-additional-construction-requirements
- ABCB Housing Provisions Standard 2022: 10.8.3(2)(c). Housing Provisions Standard 2025: 10.8.3(2)(c) and 10.8.4(3)(c)
- WA Building and Energy, Building in bushfire-prone areas (updated 31 August 2026): https://www.wa.gov.au/organisation/building-and-energy/building-bushfire-prone-areas
- Victorian Department of Transport and Planning, Building in designated bushfire prone areas: https://www.planning.vic.gov.au/guides-and-resources/guides/all-guides/building-in-bushfire-prone-areas
- Building Regulations 2018 (Vic), regs 156 and 157 (version 032, in force 27 October 2026): https://www.legislation.vic.gov.au/in-force/statutory-rules/building-regulations-2018
- Victorian Department of Transport and Planning, Building in the Bushfire Management Overlay: https://www.planning.vic.gov.au/guides-and-resources/guides/all-guides/building-in-the-bushfire-management-overlay
- NSW Rural Fire Service, Building on bush fire prone land: https://www.rfs.nsw.gov.au/plan-and-prepare/building-on-bush-fire-prone-land
- ABCB, NCC 2025 adoption dates: https://ncc.abcb.gov.au/ncc-2025/ncc-2025-state-and-territory-adoption-information
- Standards cited by number only: AS 3959:2018. The NASH Standard (Steel Framed Construction in Bushfire Areas) is cited by name only.