Fire separation between townhouses and attached houses

Editions covered: NCC 2022 (current in most states), NCC 2025 (WA, VIC, ACT) · Last reviewed 15 November 2026

Townhouses, terraces, duplexes and villa units count as Class 1a houses only because a fire-resisting wall separates them (NCC A6G2). That wall must run from the footings to the roof with no gaps. Most defects on these walls are at the top and at penetrations: framing carried through the wall, unpacked gaps under the roof sheeting, shared eaves and power points back to back. This guide sets out the NCC rules for separating walls and for external walls close to a boundary.

Which edition?

  • NCC 2022 applies in NSW, QLD, SA, TAS and the NT.
  • NCC 2025 applies in WA, VIC and the ACT from 1 May 2026. WA and the ACT allow a 12-month transition.
  • Housing Provisions Parts 9.2 and 9.3 read the same in both editions.

Where the rules are

  • NCC Volume Two H3P1: the Performance Requirement for spread of fire.
  • H3D3: fire separation of external walls, met by ABCB Housing Provisions Part 9.2.
  • H3D4: fire protection of separating walls and floors, met by Part 9.3.
  • Specification 6: fire tests for lightweight separating walls.
  • AS 1530.4 and AS 4072.1: for tested service penetrations. Cited by number only.
  • Sound insulation of separating walls is a separate requirement in Part 10.7.

Key requirements: separating walls (HP 9.3)

  1. Which walls (9.3.1(1)):
    • a wall between Class 1 buildings
    • a wall between a Class 1 building and a Class 10a building that doesn't belong to it, such as the neighbour's garage.
  2. Fire resistance (9.3.1(1)(a)): an FRL of at least 60/60/60, or masonry at least 90 mm thick. A lightweight wall must be tested to Specification 6 (9.3.1(2)).
  3. Bottom to top (9.3.1(1)(b) and (c)):
    • The wall starts at the footings or ground slab.
    • Under a non-combustible roof covering, it goes up to the underside of the covering.
    • Under a combustible roof covering, it goes at least 450 mm above the roof.
  4. At the roof (9.3.1(3)): where the wall stops under a non-combustible roof:
    • Only roof battens of 75 × 50 mm or smaller, and sarking, may cross it. Rafters, trusses and other combustible members must not.
    • Any gap at the top must be packed with mineral fibre or similar fire-resisting material.
  5. Brick veneer junction (9.3.1(4)): any gap between the separating wall and the outer veneer must:
    • be no more than 50 mm
    • be packed with mineral fibre or similar, arranged so the wall stays weatherproof.
  6. Shared eaves and verandahs (9.3.1(5)): where an eave or verandah space is open to the roof space and common to two dwellings, it must be closed off with a non-combustible vertical lining.
  7. Services through the wall (9.3.2):
    • General service openings: need construction with an FRL of at least -/60/60.
    • Cables: use a tested system, or a neatly formed hole that:
      • is at least 50 mm from other services
      • is no larger than 2,000 mm² for a single cable with a gap of no more than 15 mm, or 500 mm² in any other case
      • is packed with fire-resisting material.
    • Switches and power points: use a tested system, or meet both of these:
      • the recess is not opposite one on the other side within 300 mm horizontally or 600 mm vertically, or it goes no deeper than half the wall
      • any gap is packed.
    • Hollow walls: the cavity behind an outlet must be framed and packed (9.3.2(4)).
  8. Skylights near the wall (9.3.3): combustible roof lights must be:
    • no more than 20% of the roof area
    • at least 900 mm from the line of the separating wall.
  9. Horizontal projections (9.3.4): within 1.8 m of the wall on each side, a horizontal part of the separating construction needs one of:
    • a 60-minute resistance to the incipient spread of fire
    • an FRL of 30/30/30 from below
    • a fire-protective covering.

Key requirements: external walls near a boundary (HP 9.2)

  • When it applies (9.2.1): an external wall must be fire-resisting if it is less than:
    • 900 mm from an allotment boundary (boundaries to a road or other public space don't count)
    • 1.8 m from another building on the same allotment (with some exceptions for associated Class 10 buildings).
  • Construction (9.2.3(1) and (2)):
    • The wall runs from the footings to the underside of a non-combustible roof or eaves lining. It can stop up to 200 mm short if the gap is sealed with a non-combustible fascia, gutter or flashing.
    • It must be one of: FRL 60/60/60 from outside, 90 mm masonry veneer, or 90 mm masonry.
  • Openings (9.2.3(3) to (5)):
    • Openings in a fire-resisting external wall need non-openable fire windows (FRL -/60/-) or self-closing solid-core doors at least 35 mm thick.
    • There are limited exceptions for small windows in bathrooms, laundries and WCs.
    • Vents, weep holes and pipe penetrations are exempt.

How the states differ

  • South Australia: SA 9.2.1 adds a third trigger: an external wall less than 3 m from a brush fence must be fire-resisting. Under SA 9.2.4(4), a brush fence can't be built within 3 m of a house unless that part of the house is fire-resisting.
  • Western Australia (NCC 2025): WA adds H3D7 and WA Part 9.6, which cover the fire separation of roofed outdoor areas such as verandahs, alfresco areas and balconies (WA 9.6.2):
    • Standard distances: without a fire-resisting wall to 9.2.3, a side of the roofed outdoor area must be at least 900 mm from an allotment boundary and at least 1.8 m from another building or roofed outdoor area on the same allotment. There are exceptions, including for road and public-space boundaries and some Class 10 buildings.
    • Open, non-combustible areas: these can come as close as 500 mm to a boundary, or 1 m to another building. They need:
      • at least two sides open
      • a non-combustible structure, linings and floor
      • a polycarbonate or non-combustible roof
      • solid non-combustible screens at least 1,500 mm high along the sides that face the boundary or the other building.
    • WA 9.6.1 sets how these distances are measured. Check the details with your building surveyor.
  • NSW: NSW has its own garage-top dwelling clause (NSW H3D5), which is outside this guide. There is no variation to Part 9.3.
  • Other states and territories: no variation to Part 9.3 in the Housing Provisions schedules. A Class 2 apartment building is covered by NCC Volume One, not this guide.

Ask the app

Upload a photo of the top of the party wall, a penetration or a shared eave, or ask:

  • "Can roof trusses run over a separating wall between townhouses?"
  • "When does a fire wall need to go above the roof covering?"
  • "Can I put power points back to back in a separating wall?"
  • "When does an external wall near the boundary need to be fire rated?"
  • "What gap is allowed between a separating wall and brick veneer?"

Ask a fire question · Plastering · Builder · Electrical

Related checklists

FAQ

What fire rating does a wall between townhouses need? FRL 60/60/60, or masonry at least 90 mm thick. A lightweight system must be tested to Specification 6 (HP 9.3.1).

Does the fire wall have to go through the roof? It goes through the roof only if the roof covering is combustible, and then at least 450 mm above it. Under a non-combustible covering, it stops at the underside of the covering, with the gap packed and only small battens crossing (HP 9.3.1).

Can I run a downlight or power point in a party wall? Yes, if the outlet is a tested system, or if it isn't opposite another opening within the set distances (or goes no deeper than half the wall), with gaps packed and, in a hollow wall, the cavity behind framed and packed (HP 9.3.2).

How close to the boundary can I build without a fire-rated wall? At 900 mm or more from an allotment boundary (other than a road or public space), and 1.8 m or more from another building on the same allotment, Part 9.2 doesn't require the wall to be fire-resisting. In SA, a brush fence within 3 m also counts.

Is a townhouse Class 1 or Class 2? Under A6G2, Class 1a includes one of a group of attached dwellings, each being a building, separated by a fire-resisting wall, such as a row house, terrace house, townhouse or villa unit. A Class 2 building contains two or more sole-occupancy units (A6G3). The NCC's explanatory notes say that units stacked one above another can be Class 2 or Class 3, depending on the building. Your certifier or building surveyor confirms the classification for the project.


This is general guidance, not a compliance check. Always check your approved plans and the edition that applies to your permit, and confirm details with your certifier or building surveyor.

Based on content from the National Construction Code 2022 and 2025 (NCC Volume Two and the ABCB Housing Provisions), provided by the Australian Building Codes Board under the CC BY 4.0 licence. The ABCB does not endorse this guide. The standards the NCC references are cited and explained in our own words, not reproduced.

Sources

  • NCC 2022 Volume Two: A6G2, A6G3 and explanatory information, H3P1, H3D3, H3D4, NSW H3D5
  • ABCB Housing Provisions Standard 2022 (1 May 2023): 9.2.1, 9.2.3, 9.3.1 to 9.3.4, SA 9.2.1, SA 9.2.2(4), SA 9.2.4(4)
  • ABCB Housing Provisions Standard 2025: the same clauses were compared and no change was found. WA Part 9.6 (WA 9.6.1 and 9.6.2)
  • NCC 2025 Volume Two, Part H3 (including WA H3D7): https://ncc.abcb.gov.au/editions/ncc-2025/adopted/volume-two/h-class-1-and-10-buildings/part-h3-fire-safety
  • ABCB, NCC 2025 adoption dates: https://ncc.abcb.gov.au/ncc-2025/ncc-2025-state-and-territory-adoption-information
  • Standards cited by number only: AS 1530.4, AS 4072.1