Glazing and window safety: what the NCC asks for
Editions covered: NCC 2022 (current in most states), NCC 2025 (WA, VIC, ACT) · Last reviewed 15 November 2026
Most glazing defects found at handover come down to two questions. Is the glass in a human-impact zone safety glass, and can a child fall out of an upstairs window? This guide sets out the NCC rules for both in houses, with clauses, so glaziers, window installers and builders can check them before the labels come off.
Which edition?
- NCC 2022 applies in NSW, QLD, SA, TAS and the NT.
- NCC 2025 applies in WA, VIC and the ACT from 1 May 2026. WA and the ACT allow a 12-month transition.
- Housing Provisions Parts 8.4 and 11.3 read the same in both editions.
Where the rules are
- NCC Volume Two H1D8(1): windows and glazed doors in external walls are designed, built and installed to AS 2047. They can also follow Housing Provisions Part 8.2, within the AS 4055 geometry limits and wind class N3.
- H1D8(2): glass meets Part 8.3 or AS 1288. AS 1288 applies, for example, to:
- internal glazing
- frameless doors
- skylights
- on-site and second-hand windows
- glass balustrades and overhead glazing.
- H1D8(3): glass at risk of human impact meets AS 1288 (glass) and AS 2047 (windows), or Part 8.4.
- H5D3 and Part 11.3: barriers, including window fall protection (11.3.7 and 11.3.8).
- AS 1288 (2021 edition referenced) and AS 2047 (2014 edition) are cited by number only.
Key requirements: human impact (HP 8.4)
-
Doors (8.4.2):
- Glass in doors is Grade A safety glass.
- Unframed doors, other than shower screens, need toughened or laminated toughened glass at least 10 mm thick.
- Small annealed leadlight pieces and limited annealed panels are allowed within set sizes.
-
Side panels (8.4.3):
- Framed glass within 300 mm of the edge of a doorway is Grade A safety glass.
- Limited annealed glass is allowed where the lowest sight line is more than 1.2 m above the floor.
- Glass louvres in side panels have their own thickness rules.
-
Full-height panels (8.4.4): a panel that could be mistaken for an opening is Grade A safety glass. It isn't treated as an opening if any of these apply:
- the clear width is no more than 500 mm
- the lowest sight line is at least 500 mm above the floor
- bars, motifs or patterning make the glass obvious
- there is a chair rail at least 40 mm thick, 700 mm or more above the floor
- the floor level changes by more than 1 m across it.
-
Low glazing on the perimeter of rooms (8.4.5): framed glazing with its lowest sight line less than 500 mm above the floor must be either:
- Grade A safety glass, or
- annealed glass at least 5 mm thick, with the pane no larger than 1.2 m².
-
Bathrooms, ensuites, kitchens and spa rooms (8.4.6): this covers glazing whose lowest sight line is less than 2.0 m above the floor, bath or shower base, including shower screens, windows and cabinet doors.
- Framed panels: Grade A safety glass.
- Panels with an exposed edge: toughened glass at least 6 mm thick.
- Mirrors: plain annealed glass can be used if a fixed vanity or bench at least 760 mm high and 300 mm deep runs the full width in front.
- Splashbacks: plain annealed glass can be used if it is fully backed by and continuously adhered to a solid wall, cabinet or bench, and a fixed bench of the same minimum size runs the full width in front (8.4.6(2)).
-
Making glass visible (8.4.7):
- Glass that could be mistaken for an opening is marked with an opaque band at least 20 mm high. The band sits between 700 mm (upper edge, minimum) and 1.2 m (lower edge, maximum) above the floor.
- Exceptions include glazing no more than 1 m high or 500 mm wide, and doors with a qualifying glazing bar.
- Marking doesn't replace safety glass.
-
Labelling (8.4.8): each piece of safety glass is etched, or carries a label that can't be reused. The marking shows:
- the Standard it was tested to
- the maker or supplier
- the grade, thickness and type of glass.
Labels aren't expected to stay on after construction, so check them before handover.
Key requirements: window fall protection (HP 11.3.7 and 11.3.8)
- Bedrooms (11.3.7): protection is needed where the floor is 2 m or more above the surface outside, and the window opening is less than 1.7 m above the floor.
- The openable part needs a restricting device or a screen that doesn't let a 125 mm sphere through and resists 250 N outwards.
- If the device or screen can be removed, unlocked or overridden, it needs a child-resistant release. An 865 mm barrier is also then required at the window.
- The ABCB notes that a device fixed so it can't be undone (for example, riveted) doesn't trigger the 865 mm barrier.
- Other rooms (11.3.8): where the floor is 4 m or more above the surface outside, the openable part needs an 865 mm barrier. The barrier must not let a 125 mm sphere through or have climbable horizontal rails between 150 mm and 760 mm.
- Glass balustrades: must also meet H1D8, so AS 1288 (HP 11.3.4(10)). See our balustrades and stairs guide for heights and gaps.
How the states differ
- All states and territories: the Housing Provisions schedules list no state variation to the human-impact rules in Part 8.4 or the window rules in 11.3.7 and 11.3.8. In NCC 2025, NSW has a minor wording variation to 8.4.1(2) that changes no requirement.
- Bushfire-prone sites: AS 3959 sets extra glazing and screening rules by BAL. See our bushfire guide.
- Edition: the numbers above are the same in NCC 2022 and NCC 2025.
Ask the app
Upload a photo of the glass label, a low window or a shower screen, or ask:
- "Does a window with a sill 400 mm off the floor need safety glass?"
- "Do bathroom windows need safety glass?"
- "What does a bedroom window restrictor need to do upstairs?"
- "Can annealed glass be used for a kitchen splashback?"
- "Does a sliding door need a visibility strip?"
Ask a glazing question · Carpentry · Builder
Related checklists
- Windows, doors & glazing: new house (plan required)
- Windows, doors & glazing: renovation / extension (plan required)
- Decks, balconies & balustrades: new house (plan required)
- Related guides: Balustrades and stairs · Handover defects
FAQ
Where is safety glass required in a house? In doors, in side panels within 300 mm of a door, in full-height panels that could be mistaken for an opening, in low glazing (sight line under 500 mm, unless small 5 mm annealed panes are used), and in bathrooms, ensuites, kitchens and spa rooms below 2.0 m (HP 8.4.2 to 8.4.6).
Do bathroom windows need safety glass? Yes, if the lowest sight line is less than 2.0 m above the floor, bath or shower base. Framed panels need Grade A safety glass, and panels with exposed edges need at least 6 mm toughened glass (HP 8.4.6).
When are window restrictors required? In bedrooms where the floor is 2 m or more above the ground outside and the window opening is less than 1.7 m above the floor. In other rooms, a barrier is required once the drop is 4 m or more (HP 11.3.7 and 11.3.8).
How strong does a window restrictor need to be? It must stop a 125 mm sphere passing through and resist a 250 N outward push. If it can be released, the release must be child resistant (HP 11.3.7(2)).
How do I know if glass is safety glass? Look for the permanent etch or the non-reusable label. It shows the Standard, the maker or supplier, the grade, the thickness and the type (HP 8.4.8).
This is general guidance, not a compliance check. Always check your approved plans and the edition that applies to your permit, and confirm details with your certifier or building surveyor.
Based on content from the National Construction Code 2022 and 2025 (NCC Volume Two and the ABCB Housing Provisions), provided by the Australian Building Codes Board under the CC BY 4.0 licence. The ABCB does not endorse this guide. The standards the NCC references are cited and explained in our own words, not reproduced.
Sources
- NCC 2022 Volume Two: H1D8, H5D3
- ABCB Housing Provisions Standard 2022 (1 May 2023): 8.4.1 to 8.4.8, 11.3.4(10), 11.3.7, 11.3.8 and explanatory notes
- ABCB Housing Provisions Standard 2025: the same clauses were compared and no change was found. NSW 8.4.1(2)
- NCC 2025 Volume Two, Part H1 (H1D8): https://ncc.abcb.gov.au/editions/ncc-2025/adopted/volume-two/h-class-1-and-10-buildings/part-h1-structure
- ABCB, NCC 2025 adoption dates: https://ncc.abcb.gov.au/ncc-2025/ncc-2025-state-and-territory-adoption-information
- Standards cited by number only: AS 1288:2021, AS 2047:2014, AS 4055, AS 3959